Sun Microsystems, Inc.www.sun.comSubmit comments about this document at: http://www.sun.com/hwdocs/feedbackNetra™1290 Server InstallationGuidePart No.
x Netra 1290 Server Installation Guide • May 2006Shell PromptsTypographic ConventionsShell PromptC shell machine-name%C shell superuser machine-name#B
Preface xiRelated DocumentationThe documents listed as online are available at:http://www.sun.com/products-n-solutions/hardware/docs/Documentation, Su
xii Netra 1290 Server Installation Guide • May 2006Sun Welcomes Your CommentsSun is interested in improving its documentation and welcomes your commen
1CHAPTER1Unpacking and Installing the ServerThis chapter describes unpacking and installing the Netra 1290 server into a rack.Topics include: “Unpack
2 Netra 1290 Server Installation Guide • May 2006FIGURE 1-1 Opening the Shipping Carton4. Cut the bands from the outer packaging and open the carton.S
Chapter 1 Unpacking and Installing the Server 3FIGURE 1-2 Removing the Carton Pieces6. Remove the outer carton.SeeFIGURE 1-2.Outer cartonInternal sadd
4 Netra 1290 Server Installation Guide • May 20067. Remove the internal saddle.SeeFIGURE 1-2.8. Lift off the server bag.9. Make a visual check to ensu
Chapter 1 Unpacking and Installing the Server 5This section is divided into the following: “Adjusting the Slide Rail Assembly” on page 5 “To Install
6 Netra 1290 Server Installation Guide • May 2006Adjust the rear bracket or the adjustable bracket position to modify the length of theassembly. The s
Chapter 1 Unpacking and Installing the Server 7FIGURE 1-4 Spring Clips and CutoutsThe spring clip should engage.Note – The spring clips must be above
PleaseRecycleCopyright 2006 Sun Microsystems, Inc., 4150 Network Circle, Santa Clara, California 95054, U.S.A. All rights reserved.Sun Microsystems, I
8 Netra 1290 Server Installation Guide • May 20064. Repeat Step 1 through Step 3 for the second inner rail.▼ To Prepare the Rails for 2-Post Installat
Chapter 1 Unpacking and Installing the Server 9Installing the Slide Rail Assemblies in a Sun Fireor Sun StorEdge CabinetSun Fire™ and Sun StorEdge™ ca
10 Netra 1290 Server Installation Guide • May 20063. Insert the pins in the front bracket into cabinet holes 22 and 33 (FIGURE 1-6).FIGURE 1-6 Install
Chapter 1 Unpacking and Installing the Server 11a. Loosen the four nuts that secure the rear bracket.b. Reposition the rear bracket to the location ma
12 Netra 1290 Server Installation Guide • May 2006a. Loosen the four nuts that secure the rear bracket.b. Reposition the rear bracket to the location
Chapter 1 Unpacking and Installing the Server 13▼ To Install the Slide Rail Assemblies in the Top Position1. Remove the adjustable bracket on each rai
14 Netra 1290 Server Installation Guide • May 2006b. Discard the adjustable bracket.2. Adjust the length of each slide rail assembly.a. Loosen the fou
Chapter 1 Unpacking and Installing the Server 15▼ To Install the Slide Rail Assemblies in a 19-Inch 2-Post Rack1. Secure the front bracket with two No
16 Netra 1290 Server Installation Guide • May 2006c. Repeat Step a and Step b for the second front bezel door.FIGURE 1-8 Releasing the Door Hinge Mech
Chapter 1 Unpacking and Installing the Server 17FIGURE 1-9 Removing the Shipping Cradle Bolts▼ To Mount the Server in the CabinetCaution – The Netra 1
iiiContentsPreface ix1. Unpacking and Installing the Server 1Unpacking the Server 1Installing Slide Rails 4Adjusting the Slide Rail Assembly 5Installi
18 Netra 1290 Server Installation Guide • May 2006Caution – The shipping cradle must be attached when the server is lifted. Failure todo so will resul
Chapter 1 Unpacking and Installing the Server 19FIGURE 1-11 Aligning the RailsInner railsOuter rails
20 Netra 1290 Server Installation Guide • May 2006Caution – The cabinet stabilizers (if applicable) must be extended or the cabinetmight topple when t
Chapter 1 Unpacking and Installing the Server 2111. Press the green latches on each rail and push the server into the cabinet(FIGURE 1-13).FIGURE 1-13
22 Netra 1290 Server Installation Guide • May 200614. Reattach the front doors of the server.Installing Slide Rail Lock NutsNote – Slide rail lock nut
Chapter 1 Unpacking and Installing the Server 23FIGURE 1-15 Inserting and Tightening the Spacers5. Slide the server into the system cabinet.6. From th
24 Netra 1290 Server Installation Guide • May 2006Installing the Cable Management ArmThis section contains the following topics: “To Install the CMA–
Chapter 1 Unpacking and Installing the Server 25▼ To Install the CMA–Lite1. Secure the pivot at the end of the upper arm to the top rear of the server
26 Netra 1290 Server Installation Guide • May 2006▼ To Install the CMA–800Refer to FIGURE 1-19, throughout the following procedure for identification
Chapter 1 Unpacking and Installing the Server 271. Remove the hinge pin securing the pivot bracket to the upper CMA arm, whichfacilitates attaching th
iv Netra 1290 Server Installation Guide • May 2006Connecting Consoles to the System Controller 34Connecting the I/O Assemblies 37Installing Additional
28 Netra 1290 Server Installation Guide • May 2006FIGURE 1-21 Attaching the Upper CMA Arm and Pivot Bracket3. Remove the hinge pin securing the pivot
Chapter 1 Unpacking and Installing the Server 29FIGURE 1-22 Attaching the Lower CMA Arm and Pivot Bracket5. After attaching the bracket to the chassis
30 Netra 1290 Server Installation Guide • May 2006FIGURE 1-23 Attaching the Left-Hand T-Bracket7. Secure the right-hand T-bracket to the right-hand sl
Chapter 1 Unpacking and Installing the Server 31FIGURE 1-24 Attaching the Right-Hand T-Bracket8. Secure the upper CMA arm to the left-hand T-bracket u
32 Netra 1290 Server Installation Guide • May 2006FIGURE 1-25 Attaching the Upper and Lower CMA Arms to the T-Bracket9. Secure the lower CMA arm to th
Chapter 1 Unpacking and Installing the Server 33Connecting Power CablesCaution – The Netra 1290 server is designed to work with power systems having a
34 Netra 1290 Server Installation Guide • May 2006Note – It is the installer’s responsibility to ensure that the cabinet has sufficientelectrical powe
Chapter 1 Unpacking and Installing the Server 35LOM Serial A port connects directly to an ASCII terminal or a network terminalserver (NTS) using a com
36 Netra 1290 Server Installation Guide • May 2006FIGURE 1-26 System Controller and I/O Assembly Locations▼ To Connect the Administrative ConsoleOnce
Chapter 1 Unpacking and Installing the Server 37Connecting the I/O AssembliesThe I/O assemblies provide network interface and peripheral access to the
vFiguresFIGURE 1-1 Opening the Shipping Carton 2FIGURE 1-2 Removing the Carton Pieces 3FIGURE 1-3 Slide Rail Assembly (Standard Configuration) 5FIGURE
38 Netra 1290 Server Installation Guide • May 2006additional information refer to:http://www.sun.com/ioInstalling Additional Peripheral DevicesWhen yo
39CHAPTER2Setting UpThis chapter describes how to power on your server using the system controllercommand-line interface (LOM prompt), how to set up t
40 Netra 1290 Server Installation Guide • May 20068. Booting the Solaris Operating System.9. Installing the Lights Out Management packages from the Su
Chapter 2 Setting Up 412.0.1 Disabling Operation of the On/Standby Switch● To disable the On/Standby switch, use the setupsc command.Powering On the S
42 Netra 1290 Server Installation Guide • May 2006The server powers on completely. The System Active indicator illuminates and theserver executes the
Chapter 2 Setting Up 43▼ To Bring the System to Standby Mode From theSolaris Command Line● At the system prompt, type:▼ To Bring the System to Standby
44 Netra 1290 Server Installation Guide • May 2006● For an abrupt power off, press the left side of the On/Standby switch and hold itfor at least four
Chapter 2 Setting Up 452. At the Enter new password prompt, type your password.3. At the Enter new password again prompt, re-type your password.If you
46 Netra 1290 Server Installation Guide • May 2006Use CODE EXAMPLE 2-1 as a guide for the information you need to enter for eachparameter value entry.
Chapter 2 Setting Up 472. To power on the server, type poweron.Depending on the setting of the OpenBoot PROM auto-boot? parameter, theserver attempts
vi Netra 1290 Server Installation Guide • May 2006FIGURE 1-21 Attaching the Upper CMA Arm and Pivot Bracket 28FIGURE 1-22 Attaching the Lower CMA Arm
48 Netra 1290 Server Installation Guide • May 2006These packages are available from the Solaris software download center at:http://www.sun.com/downloa
Chapter 2 Setting Up 49i.drivers (INFO): Installing /var/tmp/SUNWlomr/reloc/platform/sun4u/kernel/drv/sparcv9/lomvi.drivers (INFO): Identified drivers
50 Netra 1290 Server Installation Guide • May 2006Note – The warning messages concerning lomp, lomv, and lom driver attachmentseen during the installa
Chapter 2 Setting Up 51CODE EXAMPLE 2-4 Installing the LOM Manual Pages# pkgadd -d . SUNWlommProcessing package instance <SUNWlomm> from </ex
52 Netra 1290 Server Installation Guide • May 2006
53APPENDIXANetra 1290 Server ConnectionsThis appendix describes the cables and connectors available to complete theinstallation. Topics include: “Ext
54 Netra 1290 Server Installation Guide • May 2006FIGURE A-1 External I/O Connection LocationsPCI+ IB_SSC AssembliesNote – Do not mix different cards
Appendix A Netra 1290 Server Connections 55SCSI ConnectorThe SCSI connector is a 68-pin SCSI connector (FIGURE A-2). TABLE A-1 lists the pinoutinforma
56 Netra 1290 Server Installation Guide • May 2006SCSI ImplementationFor PCI+ IB_SSC assemblies the embedded SCSI subsystem is a SCSI Ultra-320(Ultra
Appendix A Netra 1290 Server Connections 57NET0/NET1 Ethernet PortsThe NET0/NET1 Ethernet ports are shielded RJ-45 connectors (FIGURE A-4). TheNET0/NE
viiTablesTABLE A-1 68-Pin SCSI Connector Pinout 55TABLE A-2 68-Pin SCSI Connector Pinout (continued) 56TABLE A-3 Alarms Service Port Connector Pinout
58 Netra 1290 Server Installation Guide • May 2006FIGURE A-4 RJ-45 Gigabit Ethernet Connectors10/100BASE-T LOM Ethernet PortThe 10/100BASE-T LOM Ethe
Appendix A Netra 1290 Server Connections 59Twisted-Pair Ethernet Cable-Type ConnectivityThe following types of TPE cables can be connected to the 8-pi
60 Netra 1290 Server Installation Guide • May 2006FIGURE A-6 RJ-45 Serial ConnectorsNote – Serial port B is reserved.TABLE A-8 lists the settings nee
Appendix A Netra 1290 Server Connections 61Using a DB-25 Adapter for Your Serial LinkTo connect from a terminal, use either the DB-25 (25-Pin DSUB mal
62 Netra 1290 Server Installation Guide • May 2006
63IndexAadjusting slide rails, 5administrative console, 35alarm connector, 56Ccable lengths, 59cable management armCMA-800, installing, 26CMA-Lite, in
64 Netra 1290 Server Installation Guide • May 2006bottom position, 9, 11inner, 6lock nuts, 22Sun Fire or StorEdge cabinet, 9Sun Rack 900 cabinet, 11,
viii Netra 1290 Server Installation Guide • May 2006
ixPrefaceThe Netra 1290 Server Installation Guide provides detailed procedures that describethe installation, power-on, and configuration of the Netra